Toshiba UNINTERRUPTIBLE POWER SYSTEM 1600XP Manual do Utilizador Página 22

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 90
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 21
14
1600XP Series Installation and Operation Manual
Wire Size and Tightening Torque
Use the following table to select the recommended wire size and terminal lug tightening torque for I/O
wire connections. Use 90 °C copper conductors for all Input, Output, and Ground wiring.
Item
Terminal
Number
Cable Size - AWG
Tightening
Torque
lb.-in. (N•m)
3.6
kVA
6 kVA 8 kVA 10 kVA 14-18 kVA 22 kVA
AC Input Lines 1 and 2 10 (8) 8 (8)
8 (1/0) 6 (1/0)
4 (1/0) 1 (1/0) 14.2 (1.56)
AC Output Lines 4, 5, and 7 12 (8) 10 (8)
8 (1/0) 6 (1/0)
4 (1/0) 1 (1/0) 14.2 (1.56)
AC Output Neutral 6 12 (8) 10 (8)
8 (1/0) 6 (1/0) 4 (1/0))
1 (1/0) 14.2 (1.56)
Ground 3 and 8 12 (8) 10 (8)
8 (1/0) 6 (1/0) 4 (1/0))
1 (1/0) 14.2 (1.56)
EPO Switch 14 and 15 16 16 16 16 16 16 9.0 (0.99)
Remote Switch 16 and 17 16 16 16 16 16 16 9.0 (0.99)
Note: Wire size is presented as the recommended size followed by a bold number in () that is the maximum wire
size the terminal block can accommodate. See page 64 for knock-out hole sizes on the back of each model.
Vista de página 21
1 2 ... 17 18 19 20 21 22 23 24 25 26 27 ... 89 90

Comentários a estes Manuais

Sem comentários