7
1600XP Series Installation and Operation Manual
Installation Precautions
NOTICE
Observe the following environmental restrictions:1.
Install the unit in a well-ventilated location; allow at least 4 inches (10 cm) on all sides for air •
ventilation and for maintenance.
Install the unit where the ambient temperature is within the range specied on• pages 20 and
23.
DO NOT install the UPS in areas that are subject to high humidity.•
DO NOT install the UPS in areas that allow exposure to direct sunlight.•
DO NOT install the UPS in areas that allow exposure to high levels of airborne dust, metal •
particles, or ammable gases.
DO NOT install the UPS in areas near sources of electrical noise. Ensuring a proper earth • ground
will reduce the effects of electrical noise and will reduce the potential for electrical shock.
DO NOT install the UPS in areas that would allow uids or any foreign object to get inside the •
UPS.
UPS is intended for permanent installation only. Install the unit in a stable, level and upright position 2.
that is free of excessive vibration.
Allow at least 4 inches (100 mm) clearance on all sides of the ups 3.
for air ventilation.
Follow the instructions on the unpacking label afxed to the exterior of the UPS. 4.
WARNING
This unit contains seale d lead a cid batterie s.
La ck of p re venta tive m ainte nan ce cou ld result
in b atte ries e xplod in g a nd e mittin g ga sses an d/o r
flam e. An nu al preven tative main tena nce must be
pe rfo rm ed by a n a utho rized , tr aine d te chnician .
WARNING
CRITICAL FUSE SIZING
Incor rect fu se replacem ent size
may r esult in fire or inadeq uate
equ ipm ent protection.
Replace only with same t ype
and rating of fuse.
49455 SHEET
C AUTIO N/
A T T E N T I O N
Do not di sco nne ct
wh i le un i t is
o pe rating
on battery power.
Nes pas debrancher
sou s cha rg e.
48524 SHEET
Risk of electric shock. Do not remove cover.
. Refer servicing to qualified service personnel.
N O U S E R S E RV I C E A B L E PA R TS
IN SI DE
To reduce the risk of fire or electric shock, install in a temperature and
humidity controlled indoor area free of conduc tive contaminants.
En c as utilisation en atmosphere controlee. Consulter la notice technique.
Note: Service personnel only.
Hazardous live p arts inside the UPS are energized from the battery supply
even when the input AC power is disconnected.
Capac itors store hazardous energy. Do not remove cover until 5 minutes
after disconnecting all sources of supply.
Battery backup time, which was factory-set at a predetermined level,
decreases gradually between service periods. The batteries should be
replaced every three years after the last servicing, the date of which is
written on the ID plate lo cated on the rear side of the UPS unit, or in the
boxes below.
Date of last battery charge:
WARNING
CAUTION
Do not insert ba tte ry trays w i th the power off !
Th is uni t is de si gne d f or ho t cha n ge able ba t t e rie s!
Whe n i ns t a lli ng ba t t e ri es , t he U PS mus t b e i n th e
onlin e or bypass mode. Contact Toshiba
International Co rporation fo r further details.
6041 2
PN 51727
EXTERNAL BATTERY CABINET
The battery cabinet must have
a nominal battery voltage of
288VDC.
WARNING
DANGER/ATTENTION
Risk of electrical shock. Do not touch unin sulat ed
battery terminals. Batteries sh ould be ser viced b y
qua lified service represe ntative only. Miswiring of
battery could result in electrcal shock and/or fire.
Risque de choc electrique . Le circuit des ba tteries
nest pa s eso led e secteur. Les cosses des ba tteries
peu vent presenter une te nsion dangereuse part
rapport a la terre. Ve rifier avan t de toucher.
DANGER
Batte ry fuse is always
live. R isk of electrical
shock. Ch eck fu se
voltage and discon nect
external batteries
before changing fuse.
48518 SHEET
fig 1
fig 2
1
2
3
Unpacking Instructions
P/N 48537
TYPEFORM
OUTPUT
MFD. IN U.S.A. FROM FOREIGN AN D DOMESTIC COMPONENTS
HOUSTON, TEXAS
UNINTERRUPTIBLE POWER SUPPLY
INPUT
SERIAL NO.
PN 60 381
LIST ED
POWER
SUPPLY
27E5
C US
50802
Right
Minimum 4 in.
(100 mm)
Clearance all
sides
Front
Rear
Left