1600XP Series Installation and Operation Manual
UPS
Connections
Terminal Block
The following illustration is a detail view of the terminal block and wiring connections used for 208/240
volt units (see pages 65-66 for terminal block location).
* – If only one input line is hot, connect hot line to terminal 1 (L), and connect the Neutral line to terminal 2 (N).
NOTE 1 – If AC input power is 208 Vac rated, short terminals 11 and 12 with a jumper wire. DO NOT jumper terminal 13 to 12 or
11. Factory Setting is 208Vac. Use the jumper wire provided by Toshiba. DO NOT add any additional jumpers.
NOTE 2 – If AC input power is 240 Vac rated, short terminals 12 and 13 with a jumper wire. DO NOT jumper terminal 11 to 12 or
13. Use the jumper wire provided by Toshiba. DO NOT add any additional jumpers.
240V
208/240 Vin
REMOTE1
208
EPO2EPO1
REMOTE2
COM 240GX3
1
L2 (N*)
G X1 X2
N (0V)
2
3
12 1413 15
8765 114
16 17
L1 (L*)
120 V
240 V
120 V
208 V
208V
Jumper selection
See notes 1&2
INPUT
OUTPUT