Toshiba Tosvert VF-AS1 Manual do Utilizador Página 275

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 312
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 274
K-37
E6581301
11
[29] My function [5/5]
Vector control
Title
Communi
cation
No.
Function Adjustment range
Minimum
settin
g
unit
(
Panel/Communi
cation)
Default
settin
g
Write durin
g
runnin
g
Speed
control
Torq ue
control
PM
control
V/f Constan
t
Reference
H 0962 Analo
g
input function tar
g
et 21
0:Deselect
1:VI/II
2:RR/S4
3:RX
4:Optional AI1+, Optional AI1-
5:Optional AI2
1/1 0 Enabled /●●/●● *1
H 0964
Analog function assigned object
21
0~10 1/1 0 Disabled /●●/●● *1
H 0965 Monitor output function tar
g
et 11
2000~2099:FD00~FD99
3000~3099:FE00~FE99
1/1 2000 Enabled /●●/●● *1
H 0966
Monitor output function
command 11
0:Normal monitor, 1:Max. value, 2:Min. value 1/1 0 Enabled /●●/●● *1
H 0967 Monitor output function tar
g
et 21
2000~2099:FD00~FD99
3000~3099:FE00~FE99
1/1 2000 Enabled /●●/●● *1
H 0968
Monitor output function
command 21
0:Normal monitor, 1:Max. value, 2:Min. value 1/1 0 Enabled /●●/●● *1
H 0969 Monitor output function tar
g
et 31
2000~2099:FD00~FD99
3000~3099:FE00~FE99
1/1 2000 Enabled /●●/●● *1
H 0970
Monitor output function
command 31
0:Normal monitor, 1:Max. value, 2:Min. value 1/1 0 Enabled /●●/●● *1
H 0971 Monitor output function tar
g
et 41
2000~2099:FD00~FD99
3000~3099:FE00~FE99
1/1 2000 Enabled /●●/●● *1
H 0972
Monitor output function
command 41
0:Normal monitor, 1:Max. value, 2:Min. value 1/1 0 Enabled /●●/●● *1
H 0973 Virtual input terminal selection 1 0~135 1/1 0 Disabled /●●/●● *1
H 0974 Virtual input terminal selection 2 0~135 1/1 0 Disabled /●●/●● *1
H 0975 Virtual input terminal selection 3 0~135 1/1 0 Disabled /●●/●● *1
H 0976 Virtual input terminal selection 4 0~135 1/1 0 Disabled /●●/●● *1
H 0977 My function selection
0:Deselect
1:My function + permission signal
2: My function always ON
1/1 0 Disabled /●●/●● *1
*1: For details, refer to Instruction Manual (E6581335) specified in Section 6.41.
[30] Travenirse function
Vector control
Title
Communi
cation
No.
Function Adjustment range
Minimum
settin
g
unit
(
Panel/Communi
cation)
Default
settin
g
Write durin
g
runnin
g
Speed
control
Torq ue
control
PM
control
V/f Constan
t
Reference
H 0980 Traverse selection
0: Disabled
1: Enabled
1/1 0 Disabled / - ●● *1
H 0981 Traverse acceleration time 0.1~120.0 sec. 0.1/0.1 25.0 Enabled / - ●● *1
H 0982 Traverse deceleration time 0.1~120.0 sec. 0.1/0.1 25.0 Enabled / - ●● *1
H 0983 Traverse step 0.0~25.0% 0.1/0.1 10.0 Enabled / - ●● *1
H 0984 Traverse jump step 0.0~50.0% 0.1/0.1 10.0 Enabled / - ●● *1
*1: For details, refer to Instruction Manual (E6581337) specified in Section 6.41.
Sensorless vector/vector with sensor (:Effective, -:Ineffective)