Or. OF (Frequency Setting Parameters)
5 r.
n
5 r. n I Preset speed operation ©
Related parameters
5 r-.n
Preset speed selection
5r0 1
5r-
15
Sr-.n
Mode selection
5r-n 1
~ Sr-OF
Operating frequency settings
Operating mode settings
By changing external contact signal inputs, a max. of 15 preset speeds can be selected. (Refer to
C r-. 5 fc I f h * I for terminal allocation.)
Each speed (frequency) can be set between 0 and 400Hz.
* Note that the preset speeds cannot be set higher than the value of the max frequency | FH | • so the value
of FH I must also be changed if a higher preset speed is desired.
Basic setting method
1, Select the desired No. of speeds for preset speed operation. Sr.n ■ 0 : disabled
/~ iS : Speeds 1 to 15
2. Select the operating mode. I 5 ^ /-j
5»- r? *
U : Deactivated
/ : Activated
0 : Acc/dec #1, V/F#1, forward run
+ / : Reverse run selection
+ F : Acc/dec #2 selection
+ : V/F #2 selection
* Data setting of parameters indicated as using the *+■ mark is as follows:
Example) (+ / ) + (+P) = 3
Both reverse run and Acc/Dec #2 will be in effect when 3 is selected.
3. Set the operating frequencies for the applicable speeds between the lower limit and upper limit frequencies.
Sr-O I
15
4. Allocate the terminals for preset speed operation.
(*: D to 10 ).)
(Refer to Or. 51 It*
Preset speed No.
Terminal signal
Normal
frequency
command
1 2 3
4
5 6
7
8 9
10
11
12 13
14
15
SSI
0
0
0
0
0
0
0
0
SS2 0 0
0
0
0 0
0 0
SS3
0 0 0
0
0
0
0
0
SS4
0 0 0
0 0 0 0
0
(— = terminal-CC open, O = terminal-CC closed)
- 67 -