4. Installation and Wiring
4.1
Operating environment Do not install the T3 in the following locations :
• Where the ambient temperature drops below 0*C (32“F)
or exceeds 55‘C (13l“F)
• Where the relative humidity drops below 20% or exceeds
90%
• Where there is condensation due to sudden temperature
changes
• Where there are vibrations that exceed the tolerance of the
T3
• Where there are shocks that exceed the tolerance of the T3
• Where there are corrosive or inflammable gases
(The installation location should be below 0.05 ppm of
sulfurous acid gas, below 0.01 ppm of hydrogen sulfide.)
• Where there are dust, machining debris or other particles
• In locations exposed to direct sunlight
Observe the following precautions when installing
enclosures for mounting the T3 :
• Provide the maximum possible distance between high-
voltage or high-power panels. This distance must be at least
200 mm (8 in).
• If the enclosures are installed near high-frequency
equipment, be sure to ground the enclosures correctly.
• When sharing the channel base with other panels, check for
leakage currents from the other panels or equipment.